VIDEOS

tests and tools

Pneumatic siren test Firefighters Unidet

On 2009/11/02 at our headquarters in via Copernico 4/6 Cornaredo (MI), we carried out a functional test of our pneumatic siren (cod.36S), performed with air at a pressure of 6.5 bars. Sound pressure level measured at a distance of 1.5mt. from the same: 96/100 dB(A). Model of the sound level meter used: TES 1352 serial n° 981104934 Possible fluids/gas used: air-CO2-Nitrogen-Inert. Firefighters Unidet

Pressure test Firefighters Unidet

On 2011/03/12 at our headquarters in via copernico 4/6 cornaredo (MI), we carried out the hydraulic pressure test on our product (cod.10) Venting device for Co2 – Inerte systems. Maximum working pressure PS 370bar Maximum test pressure (1.5 times the PS) 555 bar. Fire-fighting Unidet

Hydraulic test servocontrol Firefighters Unidet

On 2011/03/24 at our headquarters in via Copernico 4/6 Cornaredo (MI), we carried out a hydraulic pressure test on our product (cod.42) Ø1/4 servocontrol hose for Co2 systems. Maximum working pressure PS 140bar Maximum test pressure (1.5 times the PS) 210 bar. Firefighters Unidet

Test of hydraulic testing of delivery hoses Firefighters Unidet

On 2011/03/24 at our headquarters in via Copernico4/6 Cornaredo (MI), was carried out a hydraulic pressure test of our product (cod. WM21.7-90°). Ø1/2 servocontrol hose for Co2 systems. Maximum working pressure PS 140bar Maximum test pressure (1.5 times the PS) 210 bar. Firefighters Unidet

Unidirectional valves test Unidet Firefighters

On 2012/02/28 At our headquarters in Via Copernico 4int.6 (MI), we carried out a test on our unidirectional valves in stainless steel 316 Antincendi unidet srl, model VRU-PG120 3/8. These valves have a PN350 but have been tested as per customer’s request at a working pressure of 50 bar. Test fluid: nitrogen in gaseous state. test with operating pressure 50bar test with test pressure 75 bar test with burst pressure 150 bar. Firefighters Unidet

Test pressure switch Firefighters Unidet

On 2011/11/09 at our headquarters in via Copernico 4/6 Cornaredo (MI), we carried out a test on our pressure switch (cod.21) with double contact with manual reset’ The test consists in verifying the intervention at minimum pressure. Fire-fighting Unidet

Test hose servocontrol Firefighters Unidet

At our headquarters in via Copernico 4/6 Cornaredo (MI), we have carried out the test of the servocontrol hose (code 41). Firefighters Unidet